Please use this identifier to cite or link to this item:
https://sci.ldubgd.edu.ua/jspui/handle/123456789/19202| Title: | DETERMINING THE EFFECT OF MODIFIED ADDITIVES ON THE FIRE-EXTINGUISHING PROPERTIES OF COMPRESSED AIR FOAM |
| Authors: | Shakhov, Stanislav Shevchuk, Viktor Dominik, Andrij |
| Keywords: | compressed air foam, mod-ified additives, fire extinguishing proper-ties, class A fires, extinguishing efficiency |
| Issue Date: | 24-Mar-2025 |
| Publisher: | Eastern-European Journal of Enterprise Technologies, |
| Series/Report no.: | 2 (10 (134)); |
| Abstract: | The object of this study is the fire extin-guishing efficiency of compressed air foam with the use of modified additives. The main hypothesis assumes that the use of modified additives in the composi-tion of the compressed air foam will affect its fire extinguishing efficiency when extin-guishing solid combustible materials.The task addressed is to determine the effect of modified additives in compressed air foam with a concentration range of 1–5% on its fire extinguishing properties. The results show that for all additives, when the concentration changes from 1% to5%, characteristic is a slight decrease in the consumption of an aqueous solution of the foaming agent. On the contrary, an increase in the expansion ratio results in a significant decrease in the mass of the aqueous solution of the foaming agent con-sumed for extinguishing. An increase in the concentration of the additive in the range of 1% to 3% is characterized by a decrease in the extinguishing time, while a further increase from 3% to 5% is characterized by an increase in the extinguishing time. Also, the increase in the foam expansion ratio has a significant effect; with an increase from 5 to 20, a decrease in the extinguish-ing time is observed, and with a further increase to 25, an increase in time occurs.For the compressed air foam with NH4H2PO4, the highest efficiency index is Ie.e≈20.15 m2/l∙s, at a modified additive con-centration of C≈3% and a foam expan-sion ratio of K≈18; for the compressed air foam with (NH4)2HPO4, the highest effi-ciency index is Ie.e=18.04 m2/l∙s, at a mod-ified additive concentration of C≈3% and a foam expansion ratio of K≈18; for a com-pression foam with (NH4)2CO3, the high-est efficiency index is Ie.e=14.99 m2/l∙s, at a modified additive concentration C≈3% and a foam expansion ratio of K≈18. Thus, based on the results of exper-imental studies, the most effective is the compressed air foam with NH4H2PO4. The resulting extinguishing efficiency is 11%higher than that of the compressed air foam with (NH4)2HPO4, and 26% high-er than that of the compressed air foam with(NH4)2CO3 |
| URI: | https://sci.ldubgd.edu.ua/jspui/handle/123456789/19202 |
| ISSN: | 1729-4061 |
| Appears in Collections: | 2025 |
Files in This Item:
| File | Description | Size | Format | |
|---|---|---|---|---|
| 325930-Article Text-762254-1-10-20250430.pdf | 2 MB | Adobe PDF | View/Open |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.